🔩 Radiographic testing (RT) of welded joints with film — test technique classes A and B, image quality indicators
In short
The joint is irradiated with X- or gamma rays and the image is recorded on radiographic film. The test is performed according to PN-EN ISO 17636-1:2023-02; Technique classes: Class A — basic techniques; class B — improved techniques, when class A is insufficiently sensitive. The procedure comprises 8 steps; it is used for: Acceptance testing of butt joints of plates and pipelines, also of nozzle welds and fillet welds, Inspection of pressure vessels, boiler drums and penstocks, Testing of circumferential welded joints of large-diameter gas pipelines.
At a glance
- Standard: PN-EN ISO 17636-1:2023-02
- Category: Materials and NDT
- Procedure steps: 8
- Technique classes: Class A — basic techniques; class B — improved techniques, when class A is insufficiently sensitive
- Minimum optical density: 2.0 for class A and 2.3 for class B in the area of interest; the maximum is limited by the capabilities of the film viewer
- Compensation for a deviation: For a deviation from a class B condition: minimum optical density 3.0 or a better film system class with a minimum density of 2.6
Overview
The standard specifies techniques of radiographic testing of fusion-welded joints in metallic materials, carried out with industrial film techniques, so that satisfactory and repeatable results are obtained. It applies to joints of plates and pipes, where "pipe" also covers other cylindrical bodies: tubes, penstocks, boiler drums and pressure vessels. The standard does not specify acceptance levels for indications visible on radiographs — these are given in the ISO 10675 series. If the contracting parties apply lower test criteria, the quality achieved may be significantly lower than when the standard is strictly applied.
The scope of the standard is broader than that of the former Polish standard PN-M-69770: it covers various metals (copper, steel, aluminium, titanium and their alloys), steel up to a thickness of 150 mm, X-rays from X-ray tubes up to 1000 kV and the isotopes Yb 169, Tm 170, Se 75, Ir 192 and Co 60, as well as X-ray sources with energies from 1 MeV to over 12 MeV. The recommended films are the equivalents of the former type II films, i.e. D5 (class C4) and D7 (class C5) according to ISO 11699-1; the maximum fog density is 0.3.
The techniques are divided into two test classes: class A (basic techniques) and class B (improved techniques), used when class A is insufficiently sensitive. The choice of class is agreed by the contracting parties. If, for technical or industrial reasons, one of the conditions of class B cannot be met, for example the type of source or the source-to-object distance, a condition of class A may be adopted with the agreement of the parties, and the loss of sensitivity compensated by raising the minimum optical density to 3.0 or by choosing a better film system class with a minimum density of 2.6. Personnel must be certified in radiographic testing according to ISO 9712 or an equivalent recognised scheme, at the level appropriate to the sector.
Method principle
X- or gamma radiation penetrates the joint under test and is attenuated according to the law of absorption, depending on the thickness and density of the material in the path of the beam. A discontinuity filled with gas or slag attenuates the beam less than solid metal, so a larger dose of energy reaches the film at that point and after photochemical processing an area of higher optical density forms; high-density inclusions, for example tungsten, give spots lighter than their surroundings. The latent image forms in an emulsion containing silver halides and becomes visible after developing and fixing. The area of interest is the weld together with the heat-affected zone on both sides — the heat-affected zone is taken as a band the width of the weld face on each side, but not less than 10 mm. Image quality is confirmed with a wire-type or step/hole-type image quality indicator (IQI): the measure of sensitivity is the number of the thinnest visible wire, a wire being considered visible when a continuous length of at least 10 mm is clearly visible in an area of uniform optical density.
Applications
- Acceptance testing of butt joints of plates and pipelines, also of nozzle welds and fillet welds
- Inspection of pressure vessels, boiler drums and penstocks
- Testing of circumferential welded joints of large-diameter gas pipelines
- Testing of tanks, loading arms and pipelines in technical inspection laboratories
- Permanent documentation of joint quality — the radiograph as verifiable evidence for the customer
Key parameters
| Parameter | Value |
|---|---|
| Technique classes | Class A — basic techniques; class B — improved techniques, when class A is insufficiently sensitive |
| Minimum optical density | 2.0 for class A and 2.3 for class B in the area of interest; the maximum is limited by the capabilities of the film viewer |
| Compensation for a deviation | For a deviation from a class B condition: minimum optical density 3.0 or a better film system class with a minimum density of 2.6 |
| Radiation sources | X-ray tubes up to 1000 kV, isotopes Yb 169, Tm 170, Se 75, Ir 192, Co 60, X-ray sources from 1 MeV to over 12 MeV |
| Material scope | Copper, steel, aluminium, titanium and their alloys; steel up to a thickness of 150 mm |
| Films and screens | Recommended films D5 (class C4) and D7 (class C5) according to ISO 11699-1; fog density maximum 0.3; typical lead screens 0.05 mm front and 0.1 mm back up to 250 kV |
| Area of interest | Weld and heat-affected zone on both sides — a band the width of the weld face, not less than 10 mm |
| Elliptical technique | Only for outside diameters up to 100 mm, wall thicknesses up to 8 mm and weld widths up to one quarter of the diameter; two images displaced by 90° are sufficient when the ratio of thickness to diameter is less than 0.12, otherwise three are needed |
Standard
- Standard number
- PN-EN ISO 17636-1:2023-02
- Title (PL)
- Badania nieniszczące spoin — Badania radiograficzne — Część 1: Techniki promieniowania X i gamma z błoną
- Title (EN)
- Non-destructive testing of welds — Radiographic testing — Part 1: X- and gamma-ray techniques with film
Step-by-step procedure
-
Radiation protection
The standard warns that exposure of any part of the body to X- or gamma rays can be highly injurious to health. Wherever X-ray equipment or radioactive sources are used, the appropriate health and safety requirements and local, national and international regulations apply.
-
Stage of manufacture and surface preparation
Surface preparation is usually not necessary, but where surface imperfections or coatings might hinder the detection of defects, the surface is ground smooth or the coatings are removed. Unless otherwise agreed, radiography is carried out after the final stage of manufacture, for example after grinding or heat treatment.
-
Selection of class and test arrangement
Agree the technique class (A or B) and select the exposure arrangement from those in the standard: single wall, double wall with a single image, double wall with a double image (elliptical and perpendicular technique), arrangements for nozzles and fillet welds. Place the films as close to the object as possible. The minimum number of radiographs for a circumferential joint is given in Annex A of the standard.
-
Marking and identification
Attach to each section of the object symbols whose images are to appear on the radiograph outside the area of interest and ensure unambiguous identification of the section. Make a permanent marking of the location of each radiograph on the object (zero point, direction, identification, measure); where the material or service conditions do not allow this, document the location with accurate sketches or photographs. When the radiograph does not show the weld, place high-density markers on both sides of it, outside the area of interest.
-
Positioning the image quality indicator
Place the wire-type or step/hole-type indicator on the source side, in the centre of the area of interest, on the parent metal next to the weld, in close contact with the surface and at a location of uniform thickness. Position the wires perpendicular to the weld so that at least 10 mm of wire length lies in an area of uniform optical density. When the indicator has to be placed on the film side, the letter F is placed next to it and this is noted in the report. When radiographing pipes with the source in the centre, it is recommended to distribute at least three indicators evenly around the circumference.
-
Exposure and film overlap
Select the voltage or source, the source-to-object distance and the exposure time for the penetrated thickness. When an area is radiographed with two or more films, ensure sufficient overlap, confirmed by a high-density marker visible on each film. Multi-film techniques are not used to shorten the exposure time on sections of uniform thickness.
-
Processing and assessment of image quality
Develop and fix the films with process control according to ISO 11699-2. Measure the optical density with a densitometer: minimum 2.0 for class A and 2.3 for class B in the area of interest. Read the number of the thinnest visible wire or the smallest visible hole and compare it with the minimum values from Annex B; with a step/hole-type indicator having two holes of the same diameter, both must be visible. Give the indicator value obtained in the report together with the type of indicator.
-
Interpretation and report
Assess the radiograph on a film viewer, classify the visible discontinuities and refer them to the acceptance levels of the ISO 10675 series (levels 1, 2, 3 correspond to the quality levels B, C and D of joints according to ISO 5817). In the report give the technique class, the source, the exposure parameters, the type and value of the image quality indicator, the optical density and the result of the assessment.
Required equipment and apparatus
| Equipment | Example | Indicative price |
|---|---|---|
| X-ray equipment | Up to 1000 kV; emits radiation only during operation, which is its advantage over isotopes | — |
| Isotope flaw detector (gamma projector) | Se 75, Ir 192, Co 60, Yb 169, Tm 170; requires no power supply, but the source radiates continuously | — |
| Radiographic films with intensifying screens | Film systems according to ISO 11699-1, lead screens selected for the radiation energy | — |
| Image quality indicators (IQI) | Wire-type according to ISO 19232-1 or step/hole-type according to ISO 19232-2; ASTM E 747 or JIS Z2306 permitted when the material group fits better | — |
| Film viewer | For viewing radiographs; minimum requirements in ISO 5580, the luminance limits the maximum density that can be assessed | — |
| Densitometer | Measurement of the optical density of the radiograph | — |
| Lead markers and high-density markers | Identification letters, letter F for an indicator on the film side, location markers and film overlap markers | — |
| Radiation protection equipment | Personal dosimeters, warning signals, fencing off of the zone, shields | — |
Reagents, media and consumables
| Reagent | CAS | Details |
|---|---|---|
| Developer | — | Solution for photochemical processing of the film, revealing the latent image; processing control according to ISO 11699-2 |
| Fixer | — | Solution fixing the image after developing |
| Rinsing water | — | For removing residual chemicals, a condition for the permanence of the radiograph as a document |
Health and safety (OHS)
- Warning in the standard: exposure of any part of the body to X- or gamma rays can be highly injurious to health
- Fencing off and marking of the controlled area, signalling of source operation, personal dosimeters and dose monitoring
- Isotope sources radiate continuously — transport container, records, storage in accordance with radiation protection regulations; an X-ray tube radiates only during operation
- Licensing and training of the operator and supervision by a radiation protection officer
- Darkroom chemicals (developer, fixer) — gloves, ventilation, collection of spent solutions as chemical waste
Frequently asked questions
Which standard describes this test?
The test is performed according to PN-EN ISO 17636-1:2023-02 — “Non-destructive testing of welds — Radiographic testing — Part 1: X- and gamma-ray techniques with film”.
How does this method work?
X- or gamma radiation penetrates the joint under test and is attenuated according to the law of absorption, depending on the thickness and density of the material in the path of the beam. A discontinuity filled with gas or slag attenuates the beam less than solid metal, so a larger dose of energy reaches the film at that point and after photochemical processing an area of higher optical density forms; high-density inclusions, for example tungsten, give spots lighter than their surroundings.
What is the measuring range and accuracy?
Technique classes: Class A — basic techniques; class B — improved techniques, when class A is insufficiently sensitive; Minimum optical density: 2.0 for class A and 2.3 for class B in the area of interest; the maximum is limited by the capabilities of the film viewer; Compensation for a deviation: For a deviation from a class B condition: minimum optical density 3.0 or a better film system class with a minimum density of 2.6; Radiation sources: X-ray tubes up to 1000 kV, isotopes Yb 169, Tm 170, Se 75, Ir 192, Co 60, X-ray sources from 1 MeV to over 12 MeV.
How long does the test take?
The procedure comprises 8 steps. The standard does not give a duration for every stage — the laboratory's own procedure decides.
What equipment is required?
X-ray equipment, Isotope flaw detector (gamma projector), Radiographic films with intensifying screens, Image quality indicators (IQI), Film viewer, Densitometer, Lead markers and high-density markers, Radiation protection equipment.
Where is this test used?
Acceptance testing of butt joints of plates and pipelines, also of nozzle welds and fillet welds; Inspection of pressure vessels, boiler drums and penstocks; Testing of circumferential welded joints of large-diameter gas pipelines; Testing of tanks, loading arms and pipelines in technical inspection laboratories; Permanent documentation of joint quality — the radiograph as verifiable evidence for the customer.
What safety precautions apply?
Warning in the standard: exposure of any part of the body to X- or gamma rays can be highly injurious to health; Fencing off and marking of the controlled area, signalling of source operation, personal dosimeters and dose monitoring; Isotope sources radiate continuously — transport container, records, storage in accordance with radiation protection regulations; an X-ray tube radiates only during operation; Licensing and training of the operator and supervision by a radiation protection officer; Darkroom chemicals (developer, fixer) — gloves, ventilation, collection of spent solutions as chemical waste.