🏗️ Tensile splitting strength of concrete

Construction PN-EN 12390-6

In short

Compression of a cylinder along a generatrix through strips of hardboard until it splits; the result fct = 2F/(π·L·d). The test is performed according to PN-EN 12390-6:2024-04; Reference specimens: Cast cylinders of Ø150×300 mm according to PN-EN 12390-1; cores of Ø ≥ 75 mm without reinforcement, an L/d ratio for cores of as little as 1 being permitted. The procedure comprises 7 steps; it is used for: Testing of pavement concrete (the WWiORB technical specifications of GDDKiA: 150 mm cubes, ≥ 3.0 MPa or ≥ 3.5 MPa), Assessment of the tensile strength of concrete in structures on cores of Ø ≥ 75 mm, Quality control of concrete in precasting and in conformity testing.

At a glance

  • Standard: PN-EN 12390-6:2024-04
  • Category: Construction
  • Procedure steps: 7
  • Reference specimens: Cast cylinders of Ø150×300 mm according to PN-EN 12390-1; cores of Ø ≥ 75 mm without reinforcement, an L/d ratio for cores of as little as 1 being permitted
  • Packing strips: Hardboard of ≥ 900 kg/m³, (15 ± 1) × (4 ± 1) mm, for single use
  • Alternative hardness criterion for the strips: An indentation of (1.2 ± 0.4) mm at a force of (20 ± 5) kN, a pin of Ø (16 ± 0.5) mm, a rate of (48 ± 10) kN/min

Overview

The standard PN-EN 12390-6 specifies a method of determining the tensile splitting strength of specimens of hardened concrete. The reference specimens are cast cylinders; cores of at least 75 mm diameter conforming to PN-EN 12504-1 may be tested by the same method, and the use of cubic and prismatic specimens is set out in Annex A. The main change of the 2023 edition (PN-EN 12390-6:2024-04) was the inclusion of the testing of cored specimens; in cases of dispute the reference method is cast cylinders of 150 mm diameter and 300 mm length.

The interlaboratory programme cited in the introduction showed that splitting between ordinary flat platens of the machine gives the same results as special curved platens (retained as an option), that the material of the packing strips affects the strength measured (hence the standardisation on hardboard, which gives the smallest deviations) and that cubes give results about 10 % higher than cast cylinders, while 150 mm cubes give lower results than 100 mm cubes.

In Polish practice 150 mm cubes are still common: the Institute of Building Materials and Concrete Technology (IMBiTB) runs proficiency tests of splitting on 3 specimens of 150×150×150 mm according to Annex A, and the WWiORB technical specifications of GDDKiA for concrete pavements require the test on cast cubes of 150 mm side with a mean of three specimens of at least 3.0 MPa (traffic categories KR1–KR4) or 3.5 MPa (KR5–KR7). It is good practice to determine the density before the test as a check on the compaction.

Method principle

A cylindrical specimen is subjected to a compressive force applied in a narrow strip along its length. The resulting perpendicular tensile force causes the specimen to fail in tension. The load is transmitted through strips of hardboard (EN 316) of a density ≥ 900 kg/m³, a width of (15 ± 1) mm and a thickness of (4 ± 1) mm, longer than the line of contact; the strips are used once only. The load is increased at a constant rate of stress of 0.04–0.06 MPa/s (the rate of loading required R = s·π·L·d/2) until the specimen can carry no greater load. The strength fct = 2F/(π·L·d), where F is the maximum load [N], L the length of the line of contact [mm] and d the cross-sectional dimension [mm]; the result is given to 0.05 MPa.

Applications

Key parameters

ParameterValue
Reference specimensCast cylinders of Ø150×300 mm according to PN-EN 12390-1; cores of Ø ≥ 75 mm without reinforcement, an L/d ratio for cores of as little as 1 being permitted
Packing stripsHardboard of ≥ 900 kg/m³, (15 ± 1) × (4 ± 1) mm, for single use
Alternative hardness criterion for the stripsAn indentation of (1.2 ± 0.4) mm at a force of (20 ± 5) kN, a pin of Ø (16 ± 0.5) mm, a rate of (48 ± 10) kN/min
Rate of stress0.04–0.06 MPa/s (±10 %), preload ≤ about 20 % of the failure load
Resultfct = 2F/(π·L·d), to 0.05 MPa
Effect of the shape of the specimenCubes about 10 % higher than cast cylinders; 150 mm cubes lower than 100 mm cubes

Standard

Standard number
PN-EN 12390-6:2024-04
Title (PL)
Badania betonu — Część 6: Wytrzymałość na rozciąganie przy rozłupywaniu próbek do badań
Title (EN)
Testing hardened concrete — Part 6: Tensile splitting strength of test specimens

Step-by-step procedure

  1. Specimens

    Cylinders conforming to PN-EN 12390-1 and PN-EN 12390-2; cores conforming to PN-EN 12504-1, of a diameter of ≥ 75 mm, without reinforcement. Examine the specimens and record any irregularities. Reject specimens outside the tolerances or correct them by grinding (irregularities) and cutting/grinding (angles).

  2. Marking of the plane of loading

    If no centring jig is used, draw two opposite lines in one axial plane, joined at both ends of the specimen, marking the plane of loading.

  3. Preparation

    Wipe excess moisture from specimens kept in water. Wipe the bearing surfaces of the jig, the strips, the loading pieces and the platens; remove any loose grains from the surface of the specimen where it makes contact with the strips.

  4. Setting up

    Place the specimen centrally in the machine (optionally in the jig) and lay the strips and any loading pieces along the upper and lower lines of the plane of loading. Ensure that the platens are parallel during loading; keep the specimen central at the first application of load with the jig or with temporary supports.

  5. Loading

    After the preload (≤ about 20 % of the failure load), increase the load without shock, continuously, at a constant rate of stress of 0.04–0.06 MPa/s (±10 %) until the specimen can carry no greater load. On manual machines correct any fall of the rate before failure; on automatic ones check the constancy of the rate from time to time.

  6. Recording and examination

    Record the maximum load. Examine the split specimens and the appearance of the concrete; record any unusual features.

  7. Calculation

    fct = 2F/(π·L·d) in MPa, to 0.05 MPa. Where the dimensions depart from those of the standard, the calculation may be based on the actual dimensions. State the type of specimen in the test report: a cast cylinder, a cube, a prism or a core.

Required equipment and apparatus

EquipmentExampleIndicative price
Testing machineA machine conforming to PN-EN 12390-4; for cubes and prisms, optionally curved steel loading pieces instead of flat platens—
Centring jig (optional)A jig positioning the cylinder and the strips without restraining the deformation of the specimen—
Packing stripsHardboard according to EN 316, density ≥ 900 kg/m³—
Cylindrical or cubic mouldsMoulds according to PN-EN 12390-1—
GrinderFor levelling irregularities and correcting the angles of the specimens—

Health and safety (OHS)

Frequently asked questions

Which standard describes this test?

The test is performed according to PN-EN 12390-6:2024-04 — “Testing hardened concrete — Part 6: Tensile splitting strength of test specimens”.

How does this method work?

A cylindrical specimen is subjected to a compressive force applied in a narrow strip along its length. The resulting perpendicular tensile force causes the specimen to fail in tension.

What is the measuring range and accuracy?

Reference specimens: Cast cylinders of Ø150×300 mm according to PN-EN 12390-1; cores of Ø ≥ 75 mm without reinforcement, an L/d ratio for cores of as little as 1 being permitted; Packing strips: Hardboard of ≥ 900 kg/m³, (15 ± 1) × (4 ± 1) mm, for single use; Alternative hardness criterion for the strips: An indentation of (1.2 ± 0.4) mm at a force of (20 ± 5) kN, a pin of Ø (16 ± 0.5) mm, a rate of (48 ± 10) kN/min; Rate of stress: 0.04–0.06 MPa/s (±10 %), preload ≤ about 20 % of the failure load.

How long does the test take?

The procedure comprises 7 steps. The standard does not give a duration for every stage — the laboratory's own procedure decides.

What equipment is required?

Testing machine, Centring jig (optional), Packing strips, Cylindrical or cubic moulds, Grinder.

Where is this test used?

Testing of pavement concrete (the WWiORB technical specifications of GDDKiA: 150 mm cubes, ≥ 3.0 MPa or ≥ 3.5 MPa); Assessment of the tensile strength of concrete in structures on cores of Ø ≥ 75 mm; Quality control of concrete in precasting and in conformity testing; Proficiency testing of laboratories (Annex A, 150 mm cubes); Estimation of the tensile strength for the design of pavements.

What safety precautions apply?

The splitting occurs suddenly — the guard of the machine and safety goggles, the hands outside the loading zone; Lay the strips and the loading pieces at zero load; do not adjust the setting under load; Cutting and grinding of concrete wet or with dust extraction.

Which laboratory can perform this test?

The test is performed by laboratories accredited to ISO/IEC 17025. On LabCoda you can find them by the standard number PN-EN 12390-6.